Spray Polyurethane Foam (SPF) is a foam insulation used to insulate spaces and maintain either cold or heat temperatures depending on the need. SPF is found on interior walls and ceilings, cold storage rooms, coolers, controlled-atmosphere rooms, general barns, and pole barns. SPF is flexible and can be applied to wood, metal, or masonry surfaces.
If it catches on fire, exposed SPF can cause more damage to a building, more extensive smoke damage to contents, and delays in firefighter response if firefighters cannot enter the building because of heavy smoke development.
While difficult to ignite directly, SPF can produce heavy smoke when exposed to a flame or heat from other fire sources. SPF fires can be short and less severe when no other material is involved. However, most structures have fuel loads that are likely to contribute to a fire.
In situations where SPF is exposed to heat for shorter durations (like a trash fire, welding torch, or hot metal), unprotected SPF can ignite and result in a flash fire. These fires are shorter in duration and produce a layer of char over the foam that is less combustible, but which still produces dangerous gas and heavy smoke that can damage contents and that will hinder firefighters.
In confined areas, combustible gases can accumulate. This can cause flashover and result in a quick spreading fire if the gas ignites. If heat and gases rise to the level of approximately 7000 degrees Fahrenheit, the initial char will provide less protection to foam underneath. It may begin contributing fuel to the fire, along with additional foam or other combustible material.
Unless proven otherwise, SPF should be treated as combustible material. Older foam applications should be suspect unless documentation can be produced.
The Spray Polyurethane Foam Alliance (SPFA) recommends foam that meets ASTM 84 Standard Test Methods for Surface Burning Characteristics of Building Material. It should have a Flame Spread Index (FSI) of 75 or less and Smoke Development Index (SDI) of 450 or less.
Note that SPFA ratings are based on laboratory conditions and not true fire situations. Even SPF with fire retardant contains organic material and will burn. One study reports the main goal of retardant is to assist with building evacuation.
Thermal barriers can both reduce the potential for the SPF to be involved in a fire and that delay smoke development. Building codes require thermal barriers in habitational buildings. Thermal barriers are intended to limit the temperature rise in SPF to not more than 250 degrees after being exposed to a fire for 15 minutes. These thermal barriers are called 15-minute thermal barriers and may also be classified as having an index of 15.
Approved thermal barriers have the equal fire resistance of 1/2 inch gypsum board. Other barriers are called ignition barriers; these do not provide the same level of protection as true thermal barriers. They may be considered acceptable in attics and crawl spaces, but do not provide the same level of protection as a true thermal barrier. Types of thermal barriers include:
Gypsum wallboard provides the best thermal barrier. It requires framework to attach and is more difficult and expensive to install. Wallboard is also susceptible to damage from forklifts or impact.
Engineered panels are made of a sandwich of metal and foam and are designed to meet requirements for limited flame spread and smoke development. They are typically found in buildings that were constructed specifically for coolers and cold-storage situations.
Engineered panels are designed and tested to meet 15-minute thermal barrier ratings. Plain corrugated metal panels can transmit heat to foam underneath and are not thermal barriers.
Spray-on or rolled-on cementitious materials are similar to sprayed or rolled fire retardant applications on structural steel. They are easier to apply but must be thick enough to provide required protection and cover all areas properly. Therefore, only trained contractors should apply the material.
Fire-treated plywood resists impact better than wallboard. Fire-retardant material can degrade over time and also requires a frame to attach to. It can be used at lower levels to resist impact with gypsum wallboard at higher levels.
Thermal barriers should be installed by qualified contractors who are familiar with the products in order to achieve the proper thickness, cover all of SPF, and properly seal seams.
These practices and controls should be applied:
We offer a wide range of Commercial insurance products. Find the product that's right for you!
Types of Business InsuranceYou need to protect more than just your business. Get insurance for your personal property too!
Personal Lines InsuranceHastings offers a range of products specifically designed for farmers.
Farm InsurancePolicyholders can request access to our On-Demand Video Training Service, which includes over 5,000 high-quality safety and human resource training videos. This service is provided at no cost to our policyholders.
View the Streamery Training Courses that are Available To get access to a Streamery course, contact your Hastings agent.
Monnit Remote Monitoring Solutions is offering Hastings policyholders a 20% discount on hardware and a 40% discount on software and connection services.
Monnit provides wireless IoT sensor solutions for remote monitoring across industries, offering real-time data tracking for temperature, humidity, motion, water detection, and more to help businesses optimize efficiency and prevent costly issues.
Hastings Insurance Company
404 E. Woodlawn Ave.
Hastings, MI 49058
Monday-Friday
8:00 a.m. - 4:30 p.m. (EST)
(800) 442-8277
Terms of Use and Privacy Statement© Hastings Insurance Company. All rights reserved.